GSSL

GSSL – 0.75” to 5.0” Deflection Vibration isolation manufacturer shall furnish integral structural steel bases. Rectangular bases are preferred for all equipment. Centrifugal refrigeration machines and pump bases may be T or L shaped. Pump bases for split case pumps shall be large enough to support suction and discharge elbows. All perimeter members shall be…

MC

MC – 0.75” to 1.0” Deflection Vibration isolation manufacturer shall furnish integral structural steel bases. Rectangular bases are preferred for all equipment. Centrifugal refrigeration machines and pump bases may be T or L shaped. Pump bases for split case pumps shall be large enough to support suction and discharge elbows. All perimeter members shall be…

MSL

MSL BASES Vibration isolation manufacturer shall furnish integral structural steel bases. Rectangular bases are preferred for all equipment. Centrifugal refrigeration machines and pump bases may be T or L shaped. Pump bases for split case pumps shall be large enough to support suction and discharge elbows. All perimeter members shall be steel beams with a…

KC

KC – 0.75” to 1.0” Deflection Vibration isolation manufacturer shall furnish integral structural steel bases. Rectangular bases are preferred for all equipment. Centrifugal refrigeration machines and pump bases may be T or L shaped. Pump bases for split case pumps shall be large enough to support suction and discharge elbows. All perimeter members shall be…

KSL

KSL – 0.75” to 3.0” Deflection Vibration isolation manufacturer shall furnish integral structural steel bases. Rectangular bases are preferred for all equipment. Centrifugal refrigeration machines and pump bases may be T or L shaped. Pump bases for split case pumps shall be large enough to support suction and discharge elbows. All perimeter members shall be…

SAST

Seismic Anchor Self Tapping Screw type anchors are preferred in floor locations so anchors can be installed after isolators or equipment is in place. Anchors shall be manufactured from hardened steel and zinc electroplated for corrosion resistance. Screw type anchors shall have an evaluation report number from the ICC-ES verifying its allowable loads. Screw type…

SAS & SASE

Seismic Anchor Stud Stud wedge anchors shall be manufactured from full diameter wire, not from undersized wire that is rolled to create the thread. The stud anchor shall also have a safety shoulder which fully supports the wedge ring under load. The stud anchor shall be zinc-coated steel for interior applications and stainless steel for…

SLDB

SLDB – Seismic Load Distribution Bracket for SCB/SSB Seismic Cable Restraints shall consist of galvanized steel aircraft cables sized to resist seismic loads with a minimum safety factor of two and arranged to provide all directional restraint. Cables must be pre-stretched to achieve a certified minimum modulus of elasticity. Cable end connections shall be steel…