SPECIFICATION 6 Restrained spring mountings shall have an SLF mounting as described in Specification 5, within a rigid housing that includes vertical limit stops to prevent spring extension when weight is removed. The housing shall serve as blocking during erection. Installed and operating heights are equal. A minimum clearance of 1/2” (12mm) shall be maintained…
SPECIFICATION 5 Spring isolators shall be free standing and laterally stable without any housing and complete with a molded neoprene cup or 1/4” (6mm) neoprene acoustical friction pad between the base- plate and the support. All mountings shall have leveling bolts that must be rigidly bolted to the equipment. Spring diameters shall be no less…
SPECIFICATION 4 A one piece molded bridge bearing neoprene washer/bushing. The bushing shall surround the anchor bolt and have a flat washer face to avoid metal to metal contact. Neoprene bushings shall be type HG as manufactured by Mason Industries, Inc.
SPECIFICATION 3 Sheet metal panels shall be bolted to the walls or supporting structure by assemblies consisting of a neoprene bushing cushioned between 2 steel sleeves. The outer sleeve prevents the sheet metal from cutting into the neoprene. Enlarge panel holes as required. Neoprene elements pass over the bushing to cushion the back panel horizontally.…
SPECIFICATION 2 Bridge-bearing neoprene mountings shall have a minimum static deflection of 0.2” (5mm) and all directional seismic capability. The mount shall consist of a ductile iron casting containing two separated and opposing molded neoprene elements. The elements shall prevent the central threaded sleeve and attachment bolt from contacting the casting during normal operation. The…
SPECIFICATION 1 Two layers of 3/4” (19mm) thick neoprene pad consisting of 2” (50mm) square waffle modules separated horizontally by a 16 (1.5mm) gauge galvanized shim. Load distribution plates shall be used as required. Pads shall be type Super “W” as manufactured by Mason Industries, Inc.
Blower Minimum Deflection Guide When blowers are 60 HP (45kw) or larger, select deflection requirements for next larger span. A minimum of 2.5” (64mm) should be used unless larger deflections are called for on the chart or these fans are located in the lowest sub-basement or on a slab on grade. Notes: 1. Minimum…