FER 501

Expansion joints installed in piping systems must be anchored on both sides of the joints to avoid the use of control rods. If control rods are installed as a safety measure, the locking nuts must be backed off with a clearance equal to the specified axial movement. The expansion joint will exert thrust on the anchors. To calculate thrust, use the following equation:

Thrust = (Thrust Area  Large End ID) x (Rated Working Pressure)

EXAMPLE— For a 12” x 10” FCR/FER500, the Thrust Area 133 in2 multiplied by the Rated Working Pressure 140 psi equals the Thrust 18,620 lbs.

133 x 140 = 18,620 lbs.

FCR 501
Tube Cover Max
Oper.
Temp.
B Butyl Butyl 250°F
E EPDM EPDM 250°F
H Hypalon Hypalon 225°F
HN Hypalon Neoprene 225°F
N Neoprene Neoprene 225°F
NH Neoprene Hypalon 225°F
Ni Nitrile Nitrile 210°F
NiN Nitrile Neoprene 210°F
NR Neoprene Natural 225°F
R Natural Natural 180°F
RN Natural Neoprene 180°F
V Viton® Viton® 250°F