GSSL - 0.75” to 5.0” Deflection

Vibration isolation manufacturer shall furnish integral structural steel bases. Rectangular bases are preferred for all equipment. Centrifugal refrigeration machines and pump bases may be T or L shaped. Pump bases for split case pumps shall be large enough to support suction and discharge elbows. All perimeter members shall be steel beams with a minimum depth equal to 1/10 of the longest dimension of the base. Base depth need not exceed 14”(350mm) provided that the deflection and misalignment is kept within acceptable limits as determined by the manufacturer. Height saving brackets shall be employed in all mounting locations to provide a base clearance of 1” (25mm). Bases shall be type WF as manufactured by Mason Industries, Inc.

FAN WHEEL Dia. Arrangement DEFLECTION Approx Ship Wt. (lbs)
0.75″-1.0″ 1.1″-2.0″ 2.1″-3.0″ 3.1″-4.0″ 4.1″-5.0″
12-24 4 & 9 300
1 740
27-36 4 & 9 470
1 950
40-49 4 & 9 740
1 1500
54-66 4 & 9 1000
1 2060
73 4 & 9 1120
1 2370
81-89 4 & 9 1760
1 3775
98 4 & 9 2400
1 5075
108 4 & 9 2600
1 5790