SLR – 5″ DEF. – 100 SERIES

Restrained spring mountings shall have an SLF mounting as described in SLF Specification, within a rigid housing that includes vertical limit stops to prevent spring extension when weight is removed. The housing shall serve as blocking during erection. Installed and operating heights are equal. Restraining Bolts shall have a neoprene bushing between the bolt and the housing. A clearance of 1/4” (6mm) shall be maintained around restraining bolts and the bushing so as not to interfere with the spring action. Limit stops shall be out of contact during normal operation. Since housings will be bolted or welded in position there must be an internal isolation pad. Housing shall be designed to resist all seismic forces. Mountings shall have an OPA preapproval from OSHPD in the state of California certifying the maximum certified horizontal and vertical load ratings. Mountings shall be type SLR or SLRS as manufactured by Mason Industries, Inc.
SIZE RATED CAPACITY (lbs) RATED DEFLATION (in) MOUNT CONSTANT (lbs/in)
174 270 lbs 5.31 in 50
175 320 lbs 5.31 in 60
176 370 lbs 5.31 in 70
177 460 lbs 5.38 in 85
178 560 lbs 5.38 in 105
179 670 lbs 5.38 in 125
180 830 lbs 5.38 in 155
181 1000 lbs 5.38 in 185
182 1240 lbs 5.37 in 230
183 1500 lbs 5.37 in 280
184 1830 lbs 5.37 in 340
185 2230 lbs 5.37 in 415
186 2710 lbs 5.37 in 505
187 3300 lbs 5.37 in 615
188 4100 lbs 5.37 in 755
189 4900 lbs 5.37 in 915
190 6000 lbs 5.37 in 1120
191 7300 lbs 5.37 in 1365
192 9000 lbs 5.37 in 1670
193 11000 lbs 5.37 in 2040
194 13300 lbs 5.37 in 2480
195 16300 lbs 5.37 in 3030
196 19800 lbs 5.37 in 3695
197 24200 lbs 5.37 in 4505
198 29000 lbs 5.37 in 5500
PRODUCT SUBMITTAL
2D CAD DETAILS
3D CAD DETAILS
MODEL STP FORMAT
REVIT RFA FORMAT

BULLETINS, DATA SHEETS & INFORMATION

SLR, SLRSO & SLRS – SPECIFICATIONS
SLR – BULLETIN
SLR – SUBMITTALS

RELATED PRODUCTS