RW30 - 1” DEF. Swing Spring Hangers
Hangers shall be as described in 10, but they shall be supplied with a combination rubber and steel rebound washer as the seismic up stop for suspended piping, ductwork, equipment and electrical cable trays. Rubber thickness shall be a minimum of 1/4” (6mm). Submittals shall include a drawing of the hanger showing the installation of the rebound washer. Hangers shall be type RW30N as manufactured by Mason Industries, Inc.
SIZE | Rated Capacity (Ibs) | Rated Defl (in) | Spring Constant (Ibs/in) | MRD (in) |
X-12 | 12 | 1.25 | 10 | 3/8 |
X-23 | 23 | 1.30 | 18 | |
X-33 | 33 | 1.10 | 30 | |
X-54 | 54 | 1.20 | 45 | |
X-76 | 76 | 1.02 | 73 | |
X-113 | 113 | 1.00 | 113 | |
X-130 | 130 | 1.00 | 130 | |
X-175 | 175 | 1.00 | 175 | |
X-210 | 210 | 1.00 | 210 | |
A-12 | 12 | 1.00 | 12 | 5/8 |
A-18 | 18 | 1.00 | 18 | |
A-25 | 25 | 1.00 | 25 | |
A-41 | 41 | 1.18 | 35 | |
A-56 | 56 | 1.14 | 49 | |
A-73 | 73 | 1.06 | 69 | |
A-95 | 95 | 1.01 | 94 | |
B-138 | 138 | 1.32 | 105 | 5/8 |
B-222 | 222 | 1.16 | 191 | |
B-278 | 278 | 1.09 | 255 | |
B-336 | 336 | 1.00 | 336 | |
B-410 | 410 | 1.07 | 385 | |
B-540 | 540 | 1.00 | 540 | |
C-630 | 630 | 1.13 | 558 | 3/4 |
C-800 | 800 | 1.00 | 800 | |
C-1010 | 1010 | 1.10 | 920 | |
C-1265 | 1265 | 1.00 | 1265 | |
D-1575 | 1575 | 1.23 | 1280 | 7/8 |
D-2150 | 2150 | 1.03 | 2095 | |
F-2760 | 2760 | 1.00 | 2760 | 7/8 |